5.2
Connecting VCN or IVS1800 Cables
VCN510
(1) Ground terminal
IVS1800
1. Connect one end of the ground cable to the grounding terminal of the device and the other
end to the grounding point of the network cabinet.
2. Connect one end of the network cable to any GE network port on the VCN510 or IVS1800.
3. Connect one end of the power cable to the power input port on the power module and the
other end to the PDU2000 in the cabinet.
Connecting a Cable to the
5.3
WLDS900 Water Sensor
1. Connect one end of the network cable
that has been routed to the water
detector to the AIDI_2 port on the
ECC800-Pro.
(2) GE1 port
(3) GE2 port
20
(4) Power button
Connecting T/H Sensor
5.4
Cables
1. Connect the OUT port on the T/H sensor on
the front door to the RS485-IN port on the
T/H sensor on the rear door in series.
(5) Power port