16.6 CUMMINS QSM11
Terminals of controller
Fuel relay output
Start relay output
CAN GND
CAN(H)
CAN(L)
Engine type: common J1939
16.7 CUMMINS QSZ13
Terminals of controller
Fuel relay output
Start relay output
Programmable output 1
Programmable output 2
CAN GND
CAN(H)
CAN(L)
Engine type: Common J1939
16.8 DETROIT DIESEL DDEC III / IV
Terminals of controller
Fuel relay output
Start relay output
CAN GND
CAN(H)
CAN(L)
Engine type: Common J1939
HGM9510 Genset Parallel Unit
HGM9510 GENSET PARALLEL UNIT
OEM connector of engine Remark
38
-
-
46
37
OEM connector of engine Remark
45
-
16&41
19&41
-
1
21
CAN port of engine
Expand
30A
battery voltage of ECU is
supplied by relay
-
-
CAN(H)
CAN(L)
ISSUE 2013-08-06
Connect with starter coil directly
CAN
line(connect
terminal only)
Using impedance 120Ω connecting line
Using impedance 120Ω connecting line
Connect to starter coil directly
Setting to idle speed control, normally
open output. Making 16 connect to 41
during high-speed running of controller
via external expansion relay.
Setting to pulse raise speed control,
normally open output. Making 19 connect
with 41 for 0.1s during high-speed
warming
expansion relay.
CAN
line(connect
terminal only)
Using impedance 120Ω connecting line
Using impedance 120Ω connecting line
Remark
relay,
Connect to starter coil directly
CAN
line(connect with controller's
only)
Using impedance 120Ω connecting line
Using impedance 120Ω connecting line
Version 1.1
communication
with
controller's
of
controller
via
communication
with
controller's
communication
Page 59 of 65
shielding
this
external
shielding
this
shielding
terminal