8 SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS

8.1 CONTENTS AND SCOPES OF PARAMETERS

Form 1
No.
Items
Timer Setting
1
Start Delay
2
Stop Delay
3
Preheat Delay
4
Cranking Time
5
Crank Rest Time
6
Safety On Delay
7
Start Idle Time
8
Warming Up Time
9
Cooling Time
10
Stop Idle Time
11
ETS Solenoid Hold (0~3600)s
12
Fail to Stop Delay
13
After Stop Time
Engine Setting
1
Engine Type
2
Flywheel Teeth
HGM9510 Genset Parallel Unit
HGM9510 GENSET PARALLEL UNIT
Parameters
Defaults
(0~3600)s
5
(0~3600)s
30
(0~3600)s
0
(3~60)s
8
(3~60)s
10
(0-3600)s
10
(0~3600)s
10
(0~3600)s
30
(0~3600)s
60
(0~3600)s
10
20
(0~3600)s
0
(0~3600)s
0
(0~39)
0
(10~300)
118
ISSUE 2013-08-06
Description
Time from mains abnormal or remote
start signal is active to start genset.
Time from mains normal or remote start
signal is inactive to stop genset.
Time of pre-powering heat plug before
starter is powered up.
Time of starter power on
The waiting time before second power
up when engine start fail.
Alarms for low oil pressure, high
temperature,
under
frequency /voltage, charge fail are
inactive.
Idle running time of genset when
starting.
Warming up time between genset switch
on and high speed running.
Radiating time before genset stop, after
it unloads.
Idle running time when genset stop.
Stop electromagnet's power on time
when genset is stopping.
Time between over of genset idle delay
and stopped when "ETS time" is set as
0;
Time between over of ETS hold delay
and stopped when "ETS Hold output
time" is not 0.
Time between genset stopped and
standby
Default:
Conventional
J1939)
When connected to J1939 engine,
choose the corresponding type.
Tooth number of the engine, for judging
Version 1.1
speed,
under
Engine(not