6.2 SHUTDOWN ALARMS

When controller detects shutdown alarm, it will send signal to open breaker and shuts down
generator.
Shutdown alarms as following:
No
Type
1
Emergency Stop
2
Over Speed
3
Under Speed
4
Loss of Speed Signal
5
Gen Over Frequency
Gen Under
6
Frequency
7
Gen Over Voltage
Genset Under
8
Voltage
9
Fail To Stop
10
Gen Over Current
11
Maintenance Due
12
ECU Shutdown
13
ECU Fail
14
Reverse Power
15
Over Power
Temperature Sensor
16
Open Circuit
17
High Temperature
HGM9510 Genset Parallel Unit
HGM9510 GENSET PARALLEL UNIT
When the controller detects an emergency stop alarm signal, it will
initiate a shutdown alarm.
When the controller detects that the generator speed has
exceeded the pre-set value, it will initiate a shutdown alarm.
When the controller detects that the generator speed has fallen
below the pre-set value, it will initiate a shutdown alarm.
When the controller detects that the engine speed is 0 and the
action select "Shutdown", it will initiate a shutdown alarm.
When the controller detects that the genset frequency has
exceeded the pre-set value, it will initiate a shutdown alarm.
When the controller detects that the genset frequency has fallen
below the pre-set value, it will initiate a shutdown alarm.
When the controller detects that the generator voltage has
exceeded the pre-set value, the controller will initiate a shutdown
alarm.
When the controller detects that the genset voltage has fallen
below the pre-set value, it will initiate a shutdown alarm.
If the engine does not fire after the pre-set number of attempts, it
will initiate a shutdown alarm.
When the controller detects that the genset current has exceeded
the pre-set value and the action select "Shutdown", it will initiate a
shutdown alarm.
When count down time is 0 and the action select "Shutdown", it
will initiate a shutdown alarm.
If an error message is received from ECU via J1939, it will initiate
a shutdown alarm.
If the module does not detect the ECU data, it will initiate a
shutdown alarm.
If reverse power detection is enabled, when the controller detects
that the reverse power value (power is negative) has fallen below
the pre-set value and the action select "Shutdown", it will initiate a
shutdown alarm.
If over power detection is enabled, when the controller detects that
the over power value (power is positive) has exceeded the pre-set
value and the action select "Shutdown", it will initiate a shutdown
alarm.
When the controller detects that the temperature sensor is open
circuit and the action select "Shutdown", it will initiate a shutdown
alarm.
When the controller detects that engine temperature has
exceeded the pre-set value, it will initiate a shutdown alarm.
ISSUE 2013-08-06
Description
Version 1.1
Page 21 of 65