15 INSTALLATION

Controller is panel built-in design; it is fixed by clips when installed. The controller's overall
dimensions and cutout dimensions for panel, please refers to as following,
1)
Battery Voltage Input
NOTE: HGM9510 controller can suit for widely range of battery voltage (8~35) VDC. Negative
of battery must be connected with the shell of starter stable. The wire's diameter must be over
2
2.5mm
and which is connected to B+ and B- of controller power. If floating charge configured,
please firstly connect output wires of charger to battery's positive and negative directly, then,
connect wires from battery's positive and negative to controller's positive and negative input ports
in order to prevent charge disturbing the controller's normal working.
2)
Speed Sensor Input
NOTE: Speed sensor is the magnetic equipment which be installed in starter and for detecting
teeth of flywheel. Its connection wires to controller should apply for 2 cores shielding line. The
shielding layer should connect to No. 16 terminal in controller while another side is hanging in air.
The else two signal wires are connected to No.17 and No.18 terminals in controller. The output
voltage of speed sensor should be within AC(1~24)V (effective value) during the full speed.
AC12V is recommended (in rated speed). When install the speed sensor, let the sensor is spun to
contacting flywheel first, then, port out 1/3 lap, and lock the nuts of sensor at last.
3)
Output And Expand Relays
CAUTION: All outputs of controller are relay contact output type. If need to expand the relays,
please add freewheel diode to both ends of expand relay's coils (when coils of relay has DC
current) or, increase resistance-capacitance return circuit (when coils of relay has AC current), in
order to prevent disturbance to controller or others equipment.
4)
AC Input
Current input of controller must be connected to outside current transformer. And the current
transformer's secondary side current must be 5A. At the same time, the phases of current