Oil Level Sensor
NOTE: User should make special declare when order controller if your genset equip with
sensor of 4~20mA.

8.5 CONDITIONS OF CRANK DINSCONNECT SELECTION

No.
0
Gen frequency
1
Speed sensor
2
Speed sensor + Gen frequency
3
Oil pressure
4
Oil pressure + Gen frequency
5
Oil pressure + Speed sensor
6
Oil pressure + Speed sensor + Gen frequency
NOTE:
a. There are 3 conditions to make starter disconnected with engine, that is, speed sensor,
generator frequency and engine oil pressure. They all can be used separately. We
recommend that engine oil pressure should be using with speed sensor and generator
frequency together, in order to make the starter motor is separated with engine immediately
and can check crank disconnect exactly.
b. Speed sensor is the magnetic equipment which be installed in starter for detecting flywheel
teeth.
c. When set as speed sensor, must ensure that the number of flywheel teeth is as same as
setting, otherwise, "over speed stop" or "under speed stop" may be caused.
d. If genset without speed sensor, please don't select corresponding items, otherwise, "start fail"
or "loss speed signal" maybe caused.
e. If genset without oil pressure sensor, please don't select corresponding items.
f. If not select generator frequency in crank disconnect setting, controller will not collect and
display the relative power quantity (can be used in water pump set); if not select speed sensor
in crank disconnect setting, the rotating speed displayed in controller is calculated by
generator frequency and number of poles.
HGM9510 Genset Parallel Unit
HGM9510 GENSET PARALLEL UNIT
Description
0 Not used
1 Custom Res Curve
2 Custom 4-20mA curve
3 SGD
4 SGH
5~15 Reserved
Setting description
ISSUE 2013-08-06
Remark
Defined resistance's range is
0~6KΩ, default is SGH sensor.
Version 1.1
Page 46 of 65