EAS Electric M-THERMAL 2 BIBLOCK Instruction Manual page 82

Table of Contents

Advertisement

Available languages

Available languages

ERROR
MALFUNCTION
CODE
OR PROTECTION
High pressure switch protection
Compressor overcurrent
protection.
High discharge temperature
protection.
Module protection
FAILURE CAUSE
AND CORRECTIVE ACTION
Heating mode, DHW mode:
1. The water flow is low; water temp is high, whether there is
air in the water system. Release the air.
2. Water pressure is lower than 0.1Mpa, charge the water to let
the pressure in the range of 0.15~0.2Mpa.
3. Over charge the refrigerant volume. Recharge the refrigerant
in right volume.
4. Electrical expansion valve locked or winding connector is
loosen. Tap-tap the valve body and plug in/ plug off the
connector for several times to make sure the valve is working
correctly. And install the winding in the right location DHW
mode: Water tank heat exchanger is smaller .Cooling mode:
1.Heat exchanger cover is not removed. Remove it.
2. Heat exchanger is dirty or something is block on the surface.
Clean the heat exchanger or remove the obstruction.
1.The same reason to P1.
2. Power supply voltage of the unit is low, increase the power
voltage to the required range.
1.The same reason to P1.
2.TW_out temp.sensor is loosen Reconnect it..
3. T1 temp.sensor is loosen. Reconnect it.
4. T5 temp.sensor is loosen. Reconnect it.
1. Power supply voltage of the unit is low, increase the power
voltage to the required range.
2. The space between the units is too narrow for heat
exchange. Increase the space between the units.
3. Heat exchanger is dirty or something is block on the surface.
Clean the heat exchanger or remove the obstruction.
4. Fan is not running. Fan motor or fan is broken, Change a
new fan or fan motor.
5. Over charge the refrigerant volume. Recharge the refrigerant
in right volume.
6. Water flow rate is low, there is air in system, or pump head
is not enough. Release the air and reselect the pump.
7. Water outlet temp.sensor is loosen or broken, reconnect it or
change a new one.
9.Module wires or screws are loosen. Reconnect wires and
screws. The thermal conductive adhesive is dry or drop.Add
some thermal conductive adhesive.
10.The wire connection is loosen or drop. Reconnect the wire.
11. Inverter module board is defective, replace a new one.
12. If already confirm the control system has no problem, then
compressor is defective, replace a new compressor.
13.The shut valves are closed,open the shut valves.
31
V.2

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

Eth10vaEth12vaEth12va-triEth16vaEth16va-tri

Table of Contents