V5 X VRF 460V 60Hz
4.9 H2, H3 Troubleshooting
Digital display output
Description
 H2 indicates that the number of slave units detected by master unit has decreased.
 H3 indicates that the number of slave units detected by master unit has increased.
 All units stop running.
 Error code is only displayed on the master unit.
Possible causes
 Some outdoor units are powered off.
 Power supply abnormal.
 Incorrect outdoor unit address setting.
 Communication wires between outdoor units not connected properly.
 Loosened wiring within electric control box.
 Damaged main PCB or electric control box communication terminals block.