intensity VRF V5 Series Service Manual page 61

Table of Contents

Advertisement

V5 X VRF 460V 60Hz
Procedure
E8
The ODU's address is not in the valid
Slave units addresses should be set from
Yes
range
1
1 to 3
No
Replace the outdoor main PCB
Notes:
1.
The master unit address should be set as 0, slave units addresses should be set from 1 to 3, and the addresses should not be repeated within one system.
Refer to Part 4, 1.1 "PCB Switches and Switch Settings".
59