Settings Menu; Iec 61850 Functional Information Mapping - Siemens Reyrolle 7SR5 Manual

Transformer protection device
Hide thumbs Also See for Reyrolle 7SR5:
Table of Contents

Advertisement

Protection and Automation Functions
5.20 81 Frequency Protection – "f>" or "f<"
Element
81-3
81-3
81-3
81-4
81-4
81-4
81-4
81-4
81-4

Settings Menu

5.20.5
Functions > Function Config
Parameter
81 Frequency
Functions > Protection > 81 > Gn 81-n
Parameter
Element
Input Selection
Operation
Setting
Hysteresis
Delay (DTL)

IEC 61850 Functional Information Mapping

5.20.6
A81PTUF*.Mod
Information
81 Frequency Enabled (Function Config)
Element Disabled
Element Inhibited
A81PTUF*.Mod.stVal
292
81-3 Hysteresis
81-3 Delay
81-3 Input Selection
81-4 Element
81-4 Operation
81-4 Setting
81-4 Hysteresis
81-4 Delay
81-4 Input Selection
Range
Enabled
Disabled
Range
Enabled
Disabled
VT1/2/3
VT4
Under
Over
40 to 70 Hz, Δ 0.01 Hz
0 to 2 %, Δ 0.1 %
0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
Setting Values
0.1 %
5 s
VT1/2/3
Enabled
Under
49 Hz
0.1 %
5 s
VT1/2/3
Settings
Default Gn1
Gn2
Disabled
Settings
Default Gn1
Gn2
Disabled
VT1/2/3
Under
49.5 Hz
0.1 %
1 s
x
0
1
x
x
x
5
5
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019
Gn3
Gn4
Gn3
Gn4
1
1
0
0
1
0
2
1