Settings Menu - Siemens Reyrolle 7SR5 Manual

Transformer protection device
Hide thumbs Also See for Reyrolle 7SR5:
Table of Contents

Advertisement

Protection and Automation Functions
5.19 67 Directional Overcurrent/Earth Fault
[dw_7SR5_function67SettingExample9, 1, en_US]
Figure 5-41
Some customers prefer to use only the sine (reactive) component of the residual current which can be easily
achieved by setting Ires Select to Ires Real to select the operating current to I
the characteristic angle ∅ to +90°.
Minimum Polarizing Voltage
The correct residual voltage direction must be measured to allow a forward/reverse decision to be made.
Minimum polarizing voltage setting can be used to prevent tripping when fault conditions are such that signif-
icant residual voltage is not generated and the directional decision would be unreliable. The setting must
allow for error in voltage measurement due to VT inaccuracy and connection. It can be used to improve
stability under non-fault conditions during unbalanced load, when earth fault elements with very sensitive
current settings are applied. This is ensured by selecting a setting which is near to the minimum expected
residual voltage during fault conditions.
High impedance earthing methods, including compensated and isolated systems, will result in high levels of
residual voltage, up to 3 times normal phase to neutral voltage, during earth faults. The minimum polarizing
voltage can therefore be increased to allow very low residual current settings to be applied without risk of
operation during unbalanced load conditions.

Settings Menu

5.19.5
Functions > Protection > 67 > Gn 67
Parameter
Char Angle
Minimum Voltage
2-out-of-3 Logic
286
Earth Fault Current In Isolated Network
Range
-95° to +95°, Δ 1°
1 V to 20 V, Δ 0.5 V
Enabled
Disabled
Settings
Default Gn1
Gn2
45°
1 V
Disabled
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019
Cos(θ - ∅) and setting
RES
Gn3
Gn4

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reyrolle 7sr54

Table of Contents