Device Functionality
3.7 Data Communications

Application and Setting Notes

3.7.3
Parameter: COM1-RS485 Protocol
Default Setting: Off
This setting is used to select the protocol used on the Com 1-RS485 interface port designated X1 on the
rear of the device.
Parameter: COM1-RS485 Station Address
Default Setting: 0
This setting is used to identify the device within the relevant range of the selected protocol.
Parameter: COM1-RS485 Baud Rate
Default Setting: 19200
This setting is used to select the baud rate, rate at which the data is transferred via the RS485 serial
connection.
Parameter: COM1-RS485 Parity
Default Setting: EVEN
This setting is used to select if a parity bit is added to the binary string to ensure the total number of bits
is even or odd and is used for error detection.
Parameter: COM1-RS485 Mode
Default Setting: Remote
This setting is used to select the operating mode of the RS485 port and is used in conjunction with the
device operating mode. Some actions are restricted on the port depending upon the ports mode and
device operating mode.
Parameter: DNP3 Unsolicited Events
Default Setting: Disabled
This setting is used enable the support of unsolicited events in DNP3 protocol.
Parameter: DNP3 Destination Address
Default Setting: 0
This setting is used to set the address of the master where the DNP3 unsolicited events are to be sent.
Parameter: DNP3 Application Timeout
Default Setting: 10
This setting is used to configure the response time of the DNP3 application layer confirmation.
122
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019