Functions > Protection > 24 > 24IT-n
Parameter
Y2 Point
X3 Point
Y3 Point
X4 Point
Y4 Point
X5 Point
Y5 Point
X6 Point
Y6 Point

IEC 61850 Functional Information Mapping

5.2.6
A24DTPVPH*.Mod
Information
24 Overexcitation Enabled (Function Config)
Inhibit 24DT-n
24DT-n Enabled
A24DTPVPH*.Mod.stVal
Device Annunciation ON/TRUE: 1
IEC 61850 Value
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019
Range
0 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 20000 s Δ 100 s
1 to 2 p.u., Δ 0.01 p.u.
0 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 20000 s Δ 100 s
1 to 2 p.u., Δ 0.01 p.u.
0 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 20000 s Δ 100 s
1 to 2 p.u., Δ 0.01 p.u.
0 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 20000 s Δ 100 s
1 to 2 p.u., Δ 0.01 p.u.
0 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 20000 s Δ 100 s
OFF/FALSE: 0
Irrelevant: x
OK: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
Protection and Automation Functions
5.2 24 Overexcitation Protection
Settings
Default Gn1
Gn2
540 s
1.21
p.u.
240 s
1.24
p.u.
120 s
1.28
p.u.
60 s
1.40
p.u.
20 s
x
0
1
x
x
x
5
5
Gn3
Gn4
1
1
0
0
1
0
2
1
155