Parameter: Delay
•
Default setting: 0.1 s
This is the time delay setting for the DTL element. This should be set to suit the individual application.
Settings Menu
5.18.5
Functions > Function Config
Parameter
59Vx Overvoltage
Functions > Protection > 59Vx > Gn 59Vx-n
Parameter
Element
Setting
Hysteresis
Delay
IEC 61850 Functional Information Mapping
5.18.6
A59VxPTOV*.Mod
Information
59Vx Overvoltage Enabled (Function Config)
Element Disabled
Element Inhibited
A59VxPTOV*.Mod.stVal
Device Annunciation ON/TRUE: 1
IEC 61850 Value
A59VxPTOV*.Health
Information
Device Healthy
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019
Range
Enabled
Disabled
Range
Enabled
Disabled
5 to 200 V, Δ 0.5 V
0 to 80 %, Δ 0.1 %
0 to 20 s Δ 0.01 s
20 to 100 s Δ 0.1 s
100 to 1000 s Δ 1 s
1000 to 10000 s Δ 10 s
10000 to 14400 s Δ 100 s
OFF/FALSE: 0
Irrelevant: x
ON: 1
BLOCKED: 2
TEST: 3
TEST/BLOCKED: 4
OFF: 5
Protection and Automation Functions
5.18 59Vx Overvoltage Protection – Vx
Settings
Default Gn1
Gn2
Disabled
Settings
Default Gn1
Gn2
Disabled
80 V
3 %
0.1 s
x
0
1
x
x
x
5
5
0
Gn3
Gn4
Gn3
Gn4
1
1
0
0
1
0
2
1
1
273