Siemens Reyrolle 7SR5 Manual page 54

Transformer protection device
Hide thumbs Also See for Reyrolle 7SR5:
Table of Contents

Advertisement

Device Functionality
3.2 Device Configuration
Configuration > Device Config
Parameter
View/edit group
Setting dependencies
Favorite meters timer
Backlight timer
Date
Time
Master time source
Master time sync lost delay
Backup time source
Backup time sync lost delay
CT1/2/3 settings display
CT4 settings display
Export power/Lag VAr
Select group mode
Clock sync from BI
Operating mode
Disk activity symbol
Unexpected Restart blocking
Unexpected restart count
Unexpected restart period
Device restart count type
Device restart count target
Trip alert
General alarm alert
Relay identifier
Circuit identifier
Setting ID
Control ID
Reset passwords
54
Range
1, 2, 3, 4
Enabled
Disabled
Off, 1, 2, 5, 10, 15, 30, 60 min
Off, 1, 2, 5, 10, 15, 30, 60 min
DD/MM/YYYY
HH:MM:SS
None, ethernet, binary input, serial
(COM1)
1 to 90 min, Δ 1 min
None, ethernet, binary input, serial
(COM1)
1 to 90 min, Δ 1 min
⋅ I
, primary, secondary
rated
⋅ I
, primary, secondary
rated
+ve/+ve, +ve/-ve, -ve/+ve, -ve/-ve
Edge triggered, level triggered
None, seconds, minutes
Out of service, local, remote, local
or remote
Enabled
Disabled
Enabled
Disabled
1 to 20
1 hr to 100 hr
(111) Power on, expected, unex-
pected
0 to 100000
Enabled
Disabled
Enabled
Disabled
<16 characters maximum>
<16 characters maximum>
Reyrolle 7SR5, Transformer Protection Device, Device Manual
Default Setting
1
Disabled
60 min
5 min
60 min
None
60 min
⋅ I
rated
⋅ I
rated
+ve/+ve
Edge triggered
None
Local or remote
Disabled
Disabled
3
1 hr
111
100
Enabled
Enabled
7SR5
<None>
Not active
Not active
No
C53000-G7040-C015-1, Edition 11.2019

Advertisement