Siemens Reyrolle 7SR5 Manual page 217

Transformer protection device
Hide thumbs Also See for Reyrolle 7SR5:
Table of Contents

Advertisement

Parameter: Setting
Default setting: 0.5 x I
This setting defines the operating current threshold of the element. The operation timing will then be
dependent on the selected delay setting.
This setting should be set to suit the individual application.
Parameter: Delay
Default setting: 0 s
This time delay setting should be set to suit the individual application.
Parameter: VTS Action
Default setting: Off
Voltage transformer failure can affect the directional decision and introduce an error. This setting selects
if operation of the 60VTS Voltage Transformer Supervision element automatically affects the operation of
the element.
Parameter Value
Off
Inhibit
Non-Dir
Parameter: 81HB2 Inhibit
Default setting: No
High levels of inrush currents into reactive components such as transformers when they are switched can
result in operation of overcurrent elements. The inrush current can be detected by a high percentage of
second harmonic current content by the 81HBL2 element. This can be configured to inhibit the overcur-
rent element automatically by configuration of this setting.
Parameter Value
No
Yes
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019
(0.5 ⋅ I
)
n
rated
Protection and Automation Functions
5.12 50G Instantaneous Earth Fault – Measured
Description
60VTS operation does not affect the element and the
forward/reverse directional decision assessed from
the applied voltage is applied regardless of the 60VTS
state. During a VT failure the device may assess the
direction incorrectly and the element may operate for
faults in the non-operate direction or not operate for
faults in the operate direction.
When 60VTS detects a VT failure the element is
immediately inhibited automatically and will not
operate. Tripping of a system fault will then rely on
other elements or devices.
When 60VTS detects a VT failure the element will
become non-directional and ignore the directional
decision. The element will operate for overcurrent
regardless of which direction the fault current is in.
Description
The earth fault element is not affected by operation
of the 81HBL2 element.
The earth fault element is inhibited by when the
81HBL2 element is operated.
217