Device Functionality
3.6 Data Storage
RDRE1.Health
Information
Device Healthy
RDRE1.Health.stVal
Device Annunciation ON/TRUE: 1
IEC 61850 Value
RDRE1.RcdMade
Information
Fault Record ready for Download
RDRE1.RcdMade.StVal
Device Annunciation ON/TRUE: 1
IEC 61850 Value
RDRE1.FltNum
Information
Fault Record Number
RDRE1.FltNum.StVal
RDRE1.GriFltNum
Information
Fault Record Number
RDRE1.GriFltNum.StVal
3.6.3

Fault Storage

Records are triggered from operation of an output relay programmed as a Trip Contact, (see
Outputs
). The Trip Alert feature must also be enabled, (see
Measured quantities for the last 100 relay trip fault records are stored with time and date of trip. Fault data
records can be viewed on the HMI LCD. These include the LED status at the time of recording.
Fault records are stored in a rolling buffer. When the buffer is full the oldest faults are overwritten.
The functionality is configured in the Configuration > Data Storage > Fault Storage menu.
114
OFF/FALSE: 0
OK: 1
WARNING: 2
ALARM: 3
OFF/FALSE: 0
Irrelevant: x
FALSE: 0
TRUE: 1
0
3
3.2 Device Configuration
Reyrolle 7SR5, Transformer Protection Device, Device Manual
C53000-G7040-C015-1, Edition 11.2019
1
1
0
1
Integer
Value
Integer
Value
3.5 Binary
).