5.3 Parameters for motor 1:P1.00-P1.37
Code
Description/Display
P1.00
Motor type selection
P1.01
Rated power
P1.02
Rated voltage
P1.03
Rated current
P1.04
Rated frequency
P1.05
Rated revolving speed
Function codes above are motor nameplate parameters. No matter VF control or vector control is the
choosen mode, users should accurately set the relating parameter according to the motor nameplate.
For better VF or vector control performance, users should tune the motor parameter. The accuracy of
the regulation results has intimate relationship with the accuracy of set motor nameplate parameters.
Asynchronous motor stator
P1.06
resistance
Asynchronous motor rotor
P1.07
resistance
Asynchronous motor
P1.08
leakage inductance
Asynchronous motor mutual
P1.09
inductance
Asynchronous motor no
P1.10
load current
P1.06~P1.10 are parameters for asynchronous motor.Generally, motor nameplate dosen't contain
such parameters, users can get them throung inverter auto tuning. Among them, 3 parameters
(P1.06~P1.08) can be get through " asynchronous motor static tuning", while all the 5 parameters as well
as encoder phase ,current loop PI etc can be get through"asynchronous motor complete tuning". When
change the motor rated power (P1.01) or motor rated voltage (P1.02), inverter would automatically
modify the P1.06~P1.10 parameter value and restore them to common standard of Y series motor
parameter.
If the asynchronous motor is unable to be tuned, users could input above parameters with factory
offeredmotor value.
P1.27
Encoder pulses number
To set ABZ or UVW incremental encoder pulse number per revolution.
In the speed sensor vector control mode, P1.27 must be set accurately.Or motor would not normally
operate.
P1.28
Encoder type
Section V. Parameter Function Table
General asynchronous motor
Variable frequency asynchronous motor
0.1kW~1000.0kW
1V~2000V
0.01A~655.35A(Inverter power≦55kW)
0.1A~6553.5A(Inverter power >55kW)
0.01Hz~maximum frequency
1rpm~65535rpm
0.001Ω~65.535Ω(Inverter power <=55kW)
0.0001Ω~6.5535Ω(Inverter power >55kW)
0.001Ω~65.535Ω(Inverter power <=55kW)
0.0001Ω~6.5535Ω(Inverter power >55kW)
0.01mH~655.35mH(Inverter power <=55kW)
0.001mH~65.535mH(Inverter power >55kW)
0.1mH~6553.5mH(Inverter power <=55kW)
0.01mH~655.35mH(Inverter power >55kW)
0.01A~P1.03(Inverter power <=55kW)
0.1A~P1.03(Inverter power >55kW)
1~ 65535
ABZ incremental encoder
UVW incremental encoder
Rotary transformer
Sine/cosine encoder
51
Setting Range
Factory
Change
Setting
Limit
0
1
0
-
-
-
-
-
-
-
-
-
-
2500
0
1
0
2
3