2.4 Wiring

The wiring of frequency inverter includes two parts: main circuit and control circuit. Users
must ensure correct connections according to the following connection diagram.

2.4.1 HV590 diagram

Circult braker
R
Three phase AC
S
power supply
T
Power grounding
Multi function input 1
Multi function input 2
Multi function input 3
Multi function input 4
Multi function input 5
Multi function input 6
Drain
drive(default)
source drive
10kΩ
P
10kΩ
P
Section II. Installation &Wiring
Braking Unit
DC reactor
R
S
T
Main circult
Control circult
DI1
2-3short-circuit(default)
AO1V 0-10V DC
DI2
1-2 short-circuit
DI3
AO1C 0-20mA DC
2-3short-circuit(default)
DI4
AO2V 0-10V DC
DI5/HD1
1-2 short-circuit
AO2C 0-20mA DC
DI6
J6
+24V
3
SP
2
CM
1
+24V
J6
3
SP
2
CM
1
J3
2-3short-circuit(default)
+10V
3
AI1V 0-10V DC
AI1
2
1-2 short-circuit
1
GND
AI1C 0-20mA DC
J4
2-3short-circuit(default)
+10V
3
485
AI1V 0-10V DC
terminal
AI2
2
resistor
1-2 short-circuit
selecting
GND
1
switch
AI1C 0-20mA DC
Shielding
cable
Fig. 2-4.1
17
optional
B
U
Morotr
V
W
Mortor grounding
J2
AO1
3
2
1
J1
3
AO2
2
GND
1
A1
Relay output1
C1
250V AC/1A
30V DC/1A
B1
A2
Relay output1
C2
250V AC/1A
30V DC/1A
B2
+24V
Y1
Relay
CM
J9
485+
3
485-
2
GND
1
Twisted shielding
P
cable
Analog output 1
P
P
Analog output 2
Modbus
communication
RS485

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents