Section V. Parameter Function Table

Caution:
The symbols in the function table are explained as follows:
"★":indicates that the parameter setup value cannot be modified when the inverter is in the
running status.
"●":indicates that the parameter value is the actual detection record and cannot be modified.
"☆":indicates that the parameter setup value can be modified when the inverter is in stop
status and running status.
"▲":indicates that the parameter is "Factory default parameter" and can be set only by the
manufacturer, and the user is forbidden to perform any operation.
"-":indicates that the parameter factory value is relevant to power or model, for specifications
please refer to corresponding parameter description.
"Change limit" indicates if the parameter is adjustable during operation.
When PP.0 is set to non-zero value, it means that the parameter protection password is set
and only when correct password is input can the user enter the parameter menu. To cancel the
password, PP.00should be set to 0.
In the user set parameter mode , parameter menu is not protected by password protection.
P group, A group are of basic function parameters, U group is the monitor function group.
5.1 Monitor function group:U0.00-U0.61
U0 parameter group is used to monitor inverter running status .Customers can check through
panel for field commissioning as well as read parameter value through communication for position
machine monitoring. Among which, U0.00~U0.31 is defined for running or stop monitor parameter
by P7.03 and P7.04.
For specific parameter function code、parameter name and minimum unit, please refer to the
table below.
Function code
U0.00
Inverter current actual setting frequency
U0.01
Inverter current actual output frequency
U0.02
Detection value of DC bus voltage
U0.03
Inverteractual output voltage
U0.04
Valid value of motor actual current
Designation
Running frequency(Hz)
Setting frequency(Hz)
DC bus voltage(V)
The output voltage(V)
Motor output current(A)
37
Unit
0.01Hz
0.01Hz
0.1V
1V
0.01A