F1 Group Motor Parameters - HNC Electric HV610 Series User Manual

Table of Contents

Advertisement

When there is a display for personality parameter mode display selection (F0 - 43), you can switch to different
parameter display modes through quick key at this time. The default value is only function parameter mode display.
F0 - 44 function code modification attribute
0: modifiable, user can modify function code through panel keyboard or communication.
1: cannot be modified. All function codes can only be viewed and cannot be modified.
F0 - 45 keyboard knob sensitivity
The greater the F0 - 45 setting, the more sensitive the keyboard shuttle (or up down operation) is, the smaller
the setting, and the less sensitive it is.
Note: this function is only valid for up and down addition and subtraction of level 0 menus, and other functions
are invalid.
F0 - 46 user password
F0 - 46 sets any non-zero number, the password protection function takes effect. The next time you enter the
menu, you must enter the password correctly, and otherwise you cannot view and modify the function parameters.
Please keep in mind the user password you have set. If F0 - 46 is set to 00000, then the set user password will be
cleared and the password protection function will be invalid.
F0 - 47 initialization
0: no operation.
1001: restore factory settings, excluding motor parameters
After setting F0 - 47 as 1001, most of the frequency inverter function parameters are restored to factory
parameters, but motor parameters, frequency command decimal point, fault record information, accumulated running
time, accumulated power-on time, and accumulated power consumption are not restored.
1002: clear record information
Clear frequency inverter fault record information, accumulated running time, accumulated power-on time, and
accumulated power consumption.
F1 - 01 rated power
F1- 02 rated voltage
F1- 03 rated current
F1 - 04 rated frequency
F1 - 05 rated rotational speed
Set the parameters of the controlled motor
In order to ensure the control function, be sure to set F1-01~F1-05 correctly according to the nameplate parameters
of the motor.
In order to obtain better VF or vector control performance, motor parameters need to be tuned, and the accuracy of
the adjustment results is closely related to the correct setting of motor nameplate parameters.
0~1 [0]
0~3 [2]
0~65535 [0]
0~65535 [0]
F1 group first motor parameters
0.1 kW ~ 1000.0 kW [ model determination ]
1V ~ 2000 V [ model determination ]
0.01A~655.35A ( frequency inverter power < = 55Kw )
0.01 Hz ~ maximum frequency [ model determination ]
1 rpm ~ 65535 rpm [ model determination ]
64

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hv610-r75g1Hv610-1r5g1Hv610-r75g2Hv610-1r5g2Hv610-2r2g2Hv610-004g2 ... Show all

Table of Contents