S1 series standard inverter
Function
code
Output terminal polarity
P06.05
Y switch-on delay
P06.06
Y switch-off delay
P06.07
HDO switch-on delay
P06.08
HDO switch-off delay
P06.09
Relay RO1 switch-on
P06.10
Relay RO1 switch-off
P06.11
Relay RO2 switch-on
P06.12
Relay RO2 switch-off
P06.13
Output terminal state of
P07.40
Digital output terminal
P17.13
Name
selection
delay
delay
delay
delay
present fault
state
Detailed parameter description
8: Frequency reached
9: Running in zero speed
10: Reach upper limit frequency
11: Reach lower limit frequency
12: Ready to run
13: In pre-exciting
14: Overload pre-alarm
15: Underload pre-alarm
16 – 17: Reserved
18: Reach set counting value
19: Reach designated counting value
20: External fault is valid
21: Reserved
22: Reach running time
23: Virtual terminal output of Modbus
communication
24 -25: Reserved
26: DC bus voltage established
27: STO action
48–63: Reserved
0x00–0x0F
0.000–50.000s
0.000–50.000s
0.000–50.000s (valid only when P06.00=1)
0.000–50.000s (valid only when P06.00=1)
0.000–50.000s
0.000–50.000s
0.000–50.000s
0.000–50.000s
/
/
-80-
Default
value
0x00
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0
0