Hitachi S1 Series Basic Manual page 131

Table of Contents

Advertisement

S1 series standard inverter
Function
Name
code
P07.02
Function of keys
Running
command
channel
P07.03
switch-over
sequence of
QUICK key
Stop function
P07.04
selection of
STOP/RST key
Displayed
P07.05
parameters 1 of
running state
Detailed parameter description
Note: After finish 1 – 4, the parameter will restore
to 0 and the uploading and downloading does not
include P29.
Range: 0x00–0x27
Ones: Function selection of QUICK/JOG key
0: No function
1: Jogging
2: Reserved
3: Forward/reverse rotation switch-over
4: Clear UP/DOWN setting
5: Coast to stop
6: Switch over the running command reference
mode in sequence
7: Reserved
Tens: Reserved
When P07.02=6, set the switch-over sequence of
running command channel.
0: keypad control→terminal control→
communication control
1: keypad control←→terminal control
2: keypad control←→communication control
3: terminal control←→communication control
Validness selection of stop function of
STOP/RST.
For fault reset, STOP/RST is valid under any
situation.
0: valid only for panel control only
1: valid for both panel and terminal control
2: valid for both panel and communication control
3: valid for all control modes
0x0000 – 0xFFFF
BIT0: running frequency (Hz on)
BIT1: set frequency (Hz flickering)
BIT2: bus voltage (Hz on)
BIT3: output voltage (V on)
BIT4: output current (A on)
BIT5: running rotation speed (rpm on)
BIT6: output power (% on)
BIT7: output torque (% on)
BIT8: PID reference (% flickering)
BIT9: PID feedback value (% on)
BIT10: input terminals state
BIT11: output terminals state
-126-
Default
Modify
value
0x01
0
0
0x03FF