S1 series standard inverter
Present reference
channel
P00.09
Max (A, B)
Min (A, B)
Note: "/" indicates this multi-function terminal is invalid under present reference channel.
When setting the auxiliary frequency inside the inverter via multi-function terminal UP (10) and
DOWN (11), users can increase/decrease the frequency quickly by setting P08.45 (UP terminal
frequency incremental change rate) and P08.46 (DOWN terminal frequency decremental change
rate).
UP terminal
function selection=10
DOWN terminal
function selection=11
Related parameter list:
Function
code
P00.03
Max. output frequency
Upper limit of running
P00.04
Lower limit of running
P00.05
A frequency command
P00.06
B frequency command
P00.07
Multi-function terminal
function 13
Channel A switches to
channel B
/
/
F
Sx
Sy
Name
frequency
frequency
selection
selection
Multi-function terminal
function 14
Combination setup
switches to channel A
A
A
UP terminal frequency incremental integral speed P08.45
DOWN terminal frequency decremental integral speed P08.46
Detailed parameter description
P00.04–400.00Hz
P00.05–P00.03
0.00Hz–P00.04
0: Set via keypad
1: Set via AI1
2: Set via AI2
3: Set via AI3
4: Set via high speed pulse HDI/HDIA
5: Reserved
6: Set via multi-step speed running
7: Set via PID control
8: Set via Modbus communication
-64-
Multi-function terminal
function 15
Combination setup
switches to channel B
B
B
T
UP terminal state
T
DOWN terminal state
T
Default
value
50.00Hz
50.00Hz
0.00Hz
2
5