S1 series standard inverter
Function
code
P05.08
Polarity of input terminal
P05.09
P05.10
Virtual terminal setting
P05.11
P05.12
S1 terminal switch-on delay
P05.13
S1 terminal switch-off delay
P05.14
S2 terminal switch-on delay
P05.15
S2 terminal switch-off delay
P05.16
S3 terminal switch-on delay
P05.17
S3 terminal switch-off delay
P05.18
S4 terminal switch-on delay
P05.19
S4 terminal switch-off delay
HDI/HDIA
P05.20
delay
HDI/HDIA
P05.21
delay
P05.22
HDIB terminal switch-on delay
Name
Digital filter time
2/3-wire control mode
terminal
switch-on
terminal
switch-off
Detailed parameter description
37: Command switches to terminal
38: Command switches to
communication
39: Pre-exciting command
40: Zero out power consumption
quantity
41: Maintain power consumption
quantity
42: Emergency stop
61: PID polarity switch-over
0x00–0x3F
0.000–1.000s
0x00–0x3F (0: disable, 1: enable)
BIT0: S1 virtual terminal
BIT1: S2 virtual terminal
BIT2: S3 virtual terminal
BIT3: S4 virtual terminal
BIT4: HDI/HDIA virtual terminal
BIT5: HDIB virtual terminal
0: 2-wire control 1
1: 2-wire control 2
2: 3-wire control 1
3: 3-wire control 2
0.000–50.000s
0.000–50.000s
0.000–50.000s
0.000–50.000s
0.000–50.000s
0.000–50.000s
0.000–50.000s
0.000–50.000s
0.000–50.000s
0.000–50.000s
0.000–50.000s
-77-
Default
value
0x00
0.010s
0x00
0
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s
0.000s