S1 series standard inverter
Function
Name
code
Reserved
P05.07
variables
Polarity of input
P05.08
terminal
P05.09
Digital filter time
Virtual terminal
P05.10
setting
Detailed parameter description
26: Wobbling frequency pause
27: Wobbling frequency reset
28: Counter reset
29: Switching between speed control and torque
control
30: Acceleration/deceleration disabled
31: Counter trigger
32: Reserved
33: Clear frequency increase/decrease setting
temporarily
34: DC brake
35: Switching between motor 1 and motor 2
36: Command switches to keypad
37: Command switches to terminal
38: Command switches to communication
39: Pre-exciting command
40: Zero out power consumption quantity
41: Maintain power consumption quantity
42: Emergency stop
43 - 60: Reserved
61: PID polarity switch-over
62-79: Reserved
0–65535
This function code is used to set the polarity of
input terminals.
When the bit is set to 0, input terminal polarity is
positive;
When the bit is set to 1, input terminal polarity is
negative;
0x000–0x3F
Set the sampling filtering time of the S1–S4,
HDIA, and .HDIB terminals. In cases where
interference is strong, increase the value of this
parameter to avoid mal-operation.
0.000–1.000s
0x000–0x3F (0: disable, 1: enable)
BIT0: S1 virtual terminal
BIT1: S2 virtual terminal
-116-
Default
Modify
value
●
0
○
0x000
○
0.010s
◎
0x00