Supported System Types; Wiring Symbols - Veris Industries E50C A Series Installation Manual

Compact power and energy meter
Table of Contents

Advertisement

Installation Guide
Power Monitoring
E50B1A, E50C2A, E50C3A
Supported System
Types
Number
of wires
Single-Phase Wiring
2
2
3
Three-Phase Wiring
3
4

Wiring Symbols

ZL0116-0A
Page 7 of 26
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
The meter has a number of different possible system wiring configurations (see Wiring section). To configure the meter, set the
System Type via the User Interface or Modbus register 130 (if so equipped). The System Type tells the meter which of its current
and voltage inputs are valid, which are to be ignored, and if neutral is connected. Setting the correct System Type prevents
unwanted energy accumulation on unused inputs, selects the formula to calculate the Theoretical Maximum System Power,
and determines which phase loss algorithm is to be used. The phase loss algorithm is configured as a percent of the Line-to-Line
System Voltage (except when in System Type 10) and also calculates the expected Line to Neutral voltages for system types that
have Neutral (12 & 40).
Values that are not valid in a particular System Type display as "----" on the User Interface or as QNAN in the Modbus registers.
CTs
Voltage Connections
Qty
ID
Qty
ID
Type
1
A
2
A, N
L-N
1
A
2
A, B
L-L
2
A, B
3
A, B, N
L-L with N 12
3
A, B, C 3
A, B, C
Delta
3
A, B, C 4
A, B, C, N Grounded
To avoid distortion, use parallel wires for control power and voltage inputs.
The following symbols are used in the wiring diagrams on the following pages.
Symbol
Voltage Disconnect Switch
Fuse (installer is responsible for ensuring compliance with local requirements. No
fuses are included with the meter.)
Earth ground
Current Transducer
X1
X2
Potential Transformer
Protection containing a voltage disconnect switch with a fuse or disconnect circuit
breaker. The protection device must be rated for the available short-circuit current at
the connection point.
NOTICE
RISK OF EQUIPMENT DAMAGE
• This product is designed only for use with U018 series current transducers (CTs).
• DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS PRODUCT.
Failure to follow these instructions can result in equipment damage.
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
System Type
Modbus
User Interface:
Register 130
SETUP>S SYS
10
1L + 1n
11
2L
2L + 1n
31
3L
40
3L + 1n
Wye
Description
Phase Loss Measurements
VLL
VLN
Balance
AN
AB
AB
AN, BN
AN-BN
AB, BC, CA
AB-BC-CA
AB, BC, CA
AN, BN, CN AN-BN-CN &
AB-BC-CA
TM
Wiring
Diagram
Diagram
number
1
2
3
4
5, 6
07132