6 Setup
Function/Configuration
Electronics and connec-
tion compartment
Adjustment of the density
range (1)
20
6
Setup
6.1
General information
The figures in brackets refer to the following illustrations.
On the electronics module you will find the following display and
adjustment elements:
•
Potentiometer for adjustment of the density range (1)
•
DIL switch for mode adjustment - min./max. (2)
•
Signal lamp (5)
Note:
As a rule, always set the mode with mode switch (2) before starting
the setup of VEGAWAVE 63. The switching output will change if you
set the mode switch (2) afterwards. This could possibly trigger other
connected instruments or devices.
6.2
Adjustment elements
5
4
Fig. 14: Electronics and connection compartment - transistor output
1
Potentiometer for adjustment of the density range
2
DIL switch for mode adjustment
3
Ground terminal
4
Connection terminals
5
Control lamp
With the potentiometer you can adapt the switching point to the solid.
It is already preset and must only be modified in special cases.
By default, the potentiometer of VEGAWAVE 63 is set to the right stop
(> 0.02 g/cm³ or 0.0008 lbs/in³). In case of very light-weight solids,
turn the potentiometer to the left stop (> 0.008 g/cm³ or 0.0003 lbs/
VEGAWAVE 63 • Transistor (NPN/PNP)
1
2
3