Setup; Indication Of The Switching Status; Simulation - Vega VEGASWING 51 Operating Instructions Manual

Vibrating level switch for liquids
Table of Contents

Advertisement

VEGASWING 51 • Transistor (PNP)
6

Setup

6.1

Indication of the switching status

The switching status of the electronics can be checked via the signal
lamps (LEDs) integrated in the upper part of the housing.
The signal lamps have the following meaning:
Green lights - voltage supply connected
Yellow lights - vibrating element covered
Red lights briefly - function test during instrument start (for approx.
1 s)
Red lights - shortcircuit or overload in the load circuit (sensor
output high-impedance)
Red flashes - Error on the vibrating element or the electronics
(sensor output high impedance)
6.2

Simulation

The VEGASWING 51 has an integrated function for simulation of the
output signal which can be activated magnetically. Please proceed as
follows:
Hold the test magnet (accessory) against the circle symbol with
the label "TEST" on the instrument housing
Fig. 14: Simulation of the output signal
The test magnet changes the current switching state of the device
for the duration of the application. You can check the change on the
control lamp. Note that the downstream devices are activated during
the simulation.
If VEGASWING 51 does not switch over after several tests with the
test magnet, you have to check the plug connection and the con-
nection cable and try it again. If there is no switching function, the
electronics will be defective. In this case you have to exchange the
electronics or return the instrument to our repair department.
6 Setup
19

Advertisement

Table of Contents
loading

Table of Contents