Only install on a solid, non-flammable surface
Max. ambient temperatures: -40 °F/+140 °F (-40 °C/+60 °C)
Relative humidity: 0–100%
The air flow direction within the inverter is from right to top (cold air intake on
the right, hot air outflow at the top). The waste air may reach a temperature of
up to 70 °C.
When installing the inverter in a switch cabinet or similar closed environment,
it is necessary to make sure that the hot air that develops will be dissipated by
forced-air ventilation
If you wish to install the inverter on the outer walls of cattle stables, it is im-
portant to keep a minimum clearance of 2 m between all sides of the inverter
and air vents and other openings.
The place of installation should not be exposed to ammonia, corrosive gases,
salts, or acids.
Example: Install-
ation of several
inverters
Do not ground
the solar mod-
ules.
-
+
+
The inverter is designed exclusively for
connection to and use with non-groun-
ded solar modules. The solar modules
must not be grounded at either the
positive or negative pole.
-