Notes on the Multi-MPP Tracker inverter

Multi MPP
Tracker – Invert-
er
DC-1
Connecting two solar module fields to a Multi
MPP Tracker inverter
Connecting multiple combined solar module
fields to a line on a Multi MPP Tracker inverter
PV 1
PV 1
PV 2
max 33 A to a single
DC terminal
DC-2
DC+1
DC+2
+
+
1
2
DC
DC
+1
+2
1
2
3 1 2 3
PV 1
PV 2
M P P T R A C K E R 2
O F F
10.0-3, 12.0-3 max. 43,5A
15.0-3,17.5-3,20.0-3 max 51A
DC+
DC-1
DC+1
42,0201,4479 42,0201,4480
Multi MPP Tracker inverters have two
independent DC inputs (MPP Tracker).
These inputs can be connected to a
number of different modules.
Each MPP Tracker has 3 DC+ termin-
als. There are a total of six DC- termin-
als.
Connecting two–six strings in Multi
MPP Tracker mode:
DC
-
Connect the strings separately to the
1 2 3 4 5 6
two MPP Tracker inputs (DC+1/DC+2).
The DC- terminals can be used as de-
sired, since they are connected intern-
ally.
Set MPP TRACKER 2 to "ON" when
starting for the first time (also sub-
sequently possible in the basic menu)
Single MPP Tracker mode on a Multi
MPP Tracker inverter:
B A S I C
If the inverter is being operated with
an external string collection box, the
DC connector kit (item numbers
42,0201,4479 and 42,0201,4480) must
DC-
be used
Set MPP TRACKER 2 to "OFF" when
starting for the first time (also sub-
sequently possible in the basic menu)
If the Multi MPP Tracker inverter is op-
erated in Single MPP Tracker mode,
the currents of the connected DC lines
are distributed evenly across both in-
puts.
37