5 ASSIGNMENT OF I/O NUMBERS
5.1.2 Q00CPU/Q01CPU
The Q00CPU/Q01CPU can configure a system with a total of five base units: one main
base unit and four extension base units.
Note that the number of usable slots (modules) is 24 slots including vacant slots.
Install modules to slots 0 - 23.
Installing any module to slot 24 or later will result in an error (SP. UNIT LAY ERR.).
Hence, the following system uses five slots, slot 0 - slot 4.
Setting of extension stage
(Refer to Section 5.2)
1
2
3
4
5 - 2
1 slot occupied
Slot No.
0 1 2 3 4
CPU slot
5 6 7 8 9
10 11 12 13 14
15 16 17 18 19
20 21 22 23
Module cannot be installed.
(Installing module will result in error.)
Q35
Q65B
Q65B
Q65B
When the GOT has been bus-connected,
one slot of extension base 1 is used.
Also one GOT occupies 16 I/O points.
Q65B
When using the GOT, consider the number
of slots and the number of I/O points.
Refer to the GOT Manual for details of bus-
connecting the GOT.
MELSEC-Q
5
5 - 2