Information: Fault Detection Circuit On; Information: Alarm Connections; Information: Rectifier Basic Information; Table 4 J1 Alarm Connection - ABB J2007003L301CB Quick Start Manual

Sps power express shelf
Table of Contents

Advertisement

QUICK START GUIDE
Information: Fault Detection
Circuit ON: Output is powered unless over loaded (power exceeds 100VA). Overloads are retested every 4 sec.
Circuit OFF: Output is unpowered.
Circuit Load Detection:
Circuits are scanned for loads upon module power up and upon manual scan.
Circuits with loads are turned ON, circuits without loads are turned OFF.
Circuit ON/OFF status is only set by scans and Manual Circuit ON/OFF actions. The last action determines the ON/
OFF state of each circuit. The only automatic change in circuit ON/OFF status occurs upon module power up.

Information: Alarm Connections

Alarm connections are on the rear of the shelf - J1 is Alarm Outputs and J2 is Alarm Inputs. Change alarm
descriptions via LAN port (Web pages) or Craft port (EasyView2) when required.
Connector
Pin
0I5R_D (5 Relays),
1
Output: R3 = Rtn
2
Output: R2 = Rtn
3
Output: R1 = Rtn
4
Output: PMN Rtn
5
Output: PMJ Rtn
6
Output: R3 = ACF
7
Output: R2 = RFA
8
Output: R1 = BD
9
Output: PMN
10
Output: PMJ
1
Only with 6 relay controllers (...6R...).
2
Returns for R1 and R4 are bridged. Other returns are isolated.
Information – Rectifier Basic Information
Rectifier
Single phase, hot-pluggable, fan-cooled
CC109165610
Note: Output Current at 54.5V. Outputs are power limited, not current limited.
Page 17
© 2021 ABB. All rights reserved.
J1 - Controller Variants
3C3R 3 Inputs, 3 Relays,
Input: PBT/TR
Input: Hi Ext. Temp.
2
Output: R1 = Rtn
Output: PMN Rtn
Output: PMJ Rtn
Input: RTNS
Input: Cust. Alrm 1
Output: R1 = BD
Output: PMN
Output: PMJ
Table 4: J1 Alarm Connections
EP1600-UTEZ: 1600W
200 - 240
Table 6: Rectifier and Plant Data
9C0R_USB 9 Inputs, no Relays
Input: Door Open
Input: Surge Protect Fail
Input: Door 2 Open
Input: Ext DC Fail Major
Input: Ext DC Fail Minor
Input: Returns
Input: Retrieve Generator
Input: Battery Fail
Input: Air Conditioner Fail
Input: External Fan Fail
Recommended
Input
Vac
A
100 - 120
15
7.5
Connector
Pin
1
2
3
4
5
6
7
8
9
10
Table 5: J2 Alarm Connections
AC Breaker
Float
A
Vdc
20
48 - 58
10
48 - 58
J2
All Controllers
Input: SPD Fail
Input: AUX MAJ
Input: Air Cond. Fail
Input: Door Open
-48V
-48V
-48V
Output: R4 = FAJ
1
Output: R4 = Rtn
1,2
Output
W
A
1200
24
1600
32
Version 1.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

J2007003l301cJ2007003l301abJ2007003l301a

Table of Contents