Table 12:
Default user roles
Role
VIEWER
OPERATOR
ENGINEER
ADMINISTRATOR
Table 13
describes the default mapping of all the user rights associated with all the
roles in the protection relay. This mapping can be modified according to the user
requirements.
Table 13:
Default roles-to-rights mapping
Rights/Roles
ADMINISTRATOR ENGINEER
Settings &
Read/Write
Configuration
Settings Group
Read/Write
Handling
Control
Read/Write
Operations
Record Handling
Read/Write
Test Mode
Read/Write
System Update
Read/Write
User
Read/Write
Management
User account information can be exported from IED Users in PCM600 to an
encrypted file which can be imported into another protection relay.
User authorization is disabled by default for the LHMI and can be
enabled with the Local override parameter via the menu path
Configuration/Authorization/Passwords. When the Local
override parameter is set to "False", Local User Account
Management comes into use.
For user authorization for PCM600, see PCM600 documentation.
The Administrator user shall not be allowed to delete the last
ADMINISTRATOR user and itself. FTP/FTPS logins are done by
entering the username and password; there is no role selection
Description
Viewing what objects are present in the logical device
Viewing what objects are present in the logical device
Performing control operations such as opening or closing the circuit
breaker
Viewing what objects are present in the logical device
Making parameter setting and configuration changes in addition to
having full access to the data sets and files
Superset of all the roles
Read/Write
Read
Read
Read/Write
Read/Write
Read
Read
Section 3
REX610 overview
OPERATOR
VIEWER
Read
Read
Read/Write
Read
Read/Write
Read
Read
Read
Read
Read
Read
Read
Read
Read
21