Section 7
Troubleshooting
60
The self-supervision signal output operates on the closed-circuit principle.
•
Normal conditions with empty application configuration
•
DIO2001 pins 16 and 17 are closed, pins 16 and 18 are open.
•
Normal conditions with application configuration
•
DIO2001 pins 16 and 17 are open, pins 16 and 18 are closed.
•
USB powered with or without application configuration
•
DIO2001 pins 16 and 18 are closed, pins 16 and 17 are open.
GUID-F300611C-FD28-484C-9BD8-3A1EF067D942 V1 EN-US
Figure 47:
Output contact
The internal fault code indicates the type of internal relay fault. When a fault
appears, the code must be recorded so that it can be reported to ABB customer
service.
The display code format for internal faults is aa.bb.cc.ddd.ee.
•
aa: Reserved for future
•
bb: Error domain
•
1: HW error
•
2: Runtime error
•
3: Communication error
•
cc: Component
•
Range 0...11
•
ddd: Error category
•
ee: Offset
2NGA000823 A
REX610
Operation Manual