Section 7
Troubleshooting
60
The self-supervision signal output operates on the closed-circuit principle.
Normal conditions with empty application configuration
DIO2001 pins 16 and 17 are closed, pins 16 and 18 are open.
Normal conditions with application configuration
DIO2001 pins 16 and 17 are open, pins 16 and 18 are closed.
USB powered with or without application configuration
DIO2001 pins 16 and 18 are closed, pins 16 and 17 are open.
GUID-F300611C-FD28-484C-9BD8-3A1EF067D942 V1 EN-US
Figure 47:
Output contact
The internal fault code indicates the type of internal relay fault. When a fault
appears, the code must be recorded so that it can be reported to ABB customer
service.
The display code format for internal faults is aa.bb.cc.ddd.ee.
aa: Reserved for future
bb: Error domain
1: HW error
2: Runtime error
3: Communication error
cc: Component
Range 0...11
ddd: Error category
ee: Offset
2NGA000823 A
REX610
Operation Manual