Line Unit Testing; Verification Without A Downstream Device; Verification With A Downstream Device - ADC WIDEBAND 3190 Installation And Verification Manual

Hide thumbs Also See for WIDEBAND 3190:
Table of Contents

Advertisement

Troubleshooting and System Testing
L
U
T
INE
NIT
ESTING
Once the line unit is installed, verify that it is operating properly. To do this, monitor the following:
Status LED
Messages reported by the front-panel display.

Verification Without a Downstream Device

If there is no downstream device installed:
Step
Procedure
1
Verify that the line unit powers up. The front-panel display illuminates and reports status messages.
2
Verify that the line unit attempts to communicate with downstream devices (status LED flashes red). Even if a downstream
device is not present, the following events should occur:
• The front-panel display reports various four-character status messages.
• The line unit again attempts communication until a downstream device is detected.

Verification With a Downstream Device

If a downstream device has been installed:
Step
Procedure
1
Verify that the line unit powers up. (The front-panel display illuminates and reports various status messages.)
2
Verify that the line unit attempts to communicate with downstream devices (status LED flashes red):
• If downstream devices are successfully identified and the loop(s) synchronizes, the line unit status LED lights a steady
green. The line unit reports normal margin messages on the front-panel display.
• If downstream devices are not successfully identified, the line unit reports status messages. The line unit attempts
communication again and reports four-character status messages until a downstream device is detected.
3
Verify that a valid DS1 signal has been applied to the line unit and the remote unit.
• If no DS1 signal is being applied to either the line unit or the remote unit inputs, then the appropriate DS1 alarms (LLOS
or RLOS) display on the front panel and the status LED flashes red.
• If a valid DS1 signal is being supplied to the line unit and remote unit, then DS1 alarm indications should be absent and
the status LED lights a steady green.
4
If you need more information on managing line units, see the user manual for the respective unit.
If you need more information on managing alarms, see
64
"Managing Alarms" on page
July 14, 2002
LTPH-SM-1052-04
65.
HMS-358 List 5 and List 6

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hms-358

Table of Contents