Sanyo MINI ECO-i SPW-CR365GXH56B Service Manual page 96

Hide thumbs Also See for MINI ECO-i SPW-CR365GXH56B:
Table of Contents

Advertisement

4. ON/OFF Controller
(SHA-KC16KAG(B))
(b) Zone registration using the system controller (SHA-KC64AG(B))
In this case, you set all Central addresses by system
controller at once manually.
(1) Press the
and
for more than 4 seconds.
and CODE No. C1 will flash.
(2) After confirming that CODE No. C1 is displayed,
press the
button. Once in this mode, a change
takes place as Fig. 9.
(3) Select the zone and group No. which you want to set
with
and
If already set, press the
(4) Set the unit No. (Indoor unit address) with
buttons, according to the zone registration table.
R.C. No. ..........................
Indoor unit No. ................
(5) Press the
button.
GROUP No. turns ON and UNIT No. (Indoor unit
address) changes from flashing to ON state. UNIT
No. is registered to selected ZONE No. and GROUP
No.
If you make mistake, then press the
reselect the ZONE, GROUP and UNIT No.
(6) Register the other UNIT No. in the same way by
following the steps (3) to (5).
(7) Finally, complete the registration by pressing the
button.
flashes for a few minutes, then OFF.
7
buttons at the same time
(GROUP) buttons.
buttons.
and
button
button
button and
7 - 36
If data is
registered
the unit No.
is displayed.
For example, in the case at left
Zone 3, group No. 7
Unit No. (indoor unit address) 2-8
Unit No. 2-8 is registered to zone 3-group 7.
Mini ECO-i System
Remote Control Functions
If no data is
registered
no number
is displayed.
Selected
group No. if
no data is
registered.
Fig. 9
Fig. 10