13. Serial-Parallel I/O Unit
(ACC-SP16TAG(B))
(3) Connecting the Serial-Parallel I/O Unit with the Remote Stations
Serial-Parallel I/O Unit side
Input/
output item
Input/output conditions
Start output
Status
Alarm output
output
No-voltage a-contact
static
Allowable contact
voltage and current:
DC 30 V, 0.5 A
(Minimum load: 1 V, 1 mA)
COS output (answerback)
No-voltage a-contact
static
Allowable contact
voltage and current:
DC 30 V, 0.5 A
(Minimum load: 1 V, 1 mA)
Filter sign output
Allowable contact
voltage and current:
DC 30 V, 0.5 A
(Minimum load: 1 V, 1 mA)
Start input
Control
Stop input
input
Voltage a-contact
pulses
Allowable contact
voltage and current:
DC 24 V, 10 mA
Central input
Voltage a-contact
static
Allowable contact
voltage and current:
DC 24 V, 10 mA
*1
Emergency stop input
Voltage a-contact
static
Allowable contact
voltage and current:
DC 24 V, 10 mA
Indoor temperature
Analog
monitor output
output
Output current:4 to 20 mA
*3
Temperature indication range:
5 to 36
, 0.5
step
Input impedance:250
Remote controller sensor:
Remote controller
On-the-body sensor:
Air intake temperature
Indoor temperature
Analog
setting input
input
Input voltage:1 to 5 V
*2
Temperature setting range:
Within the indoor
temperature setting range
Temperature reading:
In steps of 1
Input impedance:1M
The length of a wire that connects a Serial/Parallel I/O unit and the
equipment should be less than 50 m for analog signal, and less than
100 m for digital signal.
*1 About Emergency Stop Signal
This signal immediately stops all indoor units connected to the
Serial/Parallel I/O unit and disables any manual operations through the
remote controller. When this signal is off, manual operations through
remote controllers become enabled.
*2 About Temperature Setting Input (analog input)
When the setting signal for room temperature is within DC1 - 5 V, the
setting value is sent to the applicable group, and each air conditioner in
the group sets a setting temperature within a predetermined range for
the air conditioner. Temperature is indicated in 1°C intervals. Check the
precision (resolution) of the central monitor. When a signal more than
1.0 V is inputted, temperature setting can not be carried out with the
remote controller that shows the sign, "Under Centralized Control". With
a signal less than 1.0 V, temperature setting can be made with the
remote controller.
30
7
10
1.0
*3 About the Room Temperature Monitor (analog output)
The current of the room temperature monitor signal is within DC4 - 20
mA (5 - 35 ). And temperature is indicated in 0.5
precision (resolution) of the central monitor.
Remote Station side
Terminal number
Isolating terminal
Example circuit
CPEV0.9
1.2
12P-1
12P-2
D i gi t al
i n put
12P-3
CPEV0.9
1.2
12P-4
D i gi t al
12P-5
i n pu t
CPEV0.9
1.2
12P-6
D i gi t al
12P-7
i n pu t
+24V
CPEV0.9
1.2
12P-8
CX
12P-9
TX
COM
12P-10
CPEV0.9
1.2
Remote contr-
+24V
oller disabled
12P-11
on rising and
CX
enabled on
falling of static
12P-12
input
COM
Operation
CPEV0.9
1.2
+24V
stopped and
remote controller
12P-8
disabled on rising
CX
and remote contr-
oller enabled on
12P-9
falling of static
COM
input
Analog outputs
CPEV-S0.9
1.2
for 16 units are
B(+)
provided. Use
Insulated
insulated
analog
individual
input
analog input.
A(-)
G
Analog inputs
CPEV-S0.9
1.2
B(+)
for 16 units are
Analog
provided. Use
output
within 0.1%
of reference
A(-)
accuracy
G
Enable the remote controller
to set temperature
Disable the remote controller
from setting temperature
3.0 V
intervals. Check the
4. About Setting Switches and Display
Digital circuit board
Changing of the disabled mode of
Input/Output
remote controller temperature setting
Condition
SW3
SW2
1
8
1
Response
time for
start/stop
input:
Spare
Max.40
seconds
Response
time for
start/stop
input:
Max.1
About Setting Switches (SW1)
second
ON
ON with
1
2
3
4
5
a filter sign
Pulse width:
300 msec or
longer
Zone address switch
Zone address
1 (Central control address 1-16)
2 (Central control address 17-32)
3 (Central control address 33-48)
4 (Central control address 49-64)
About Setting of SW2 and SW3
Spare switch: Be sure that all switches are turned off to use.
5. Zone Address Setting Switch of Serial-Parallel I/O
When controlling the Serial/Parallel I/O units in two or more zones, set the
zone address for each unit (setting switches No. 1 and 2 on SW1).
To control a Serial/Parallel I/O unit in only one zone, adjust the setting of
the unit for Zone 1.
To control Serial/Parallel I/O units in two or more zones, adjust the setting
of one of the Serial/Parallel I/O units for Zone 1.
Serial/Parallel I/O SW1
ON
Zone1
OFF
1 2
ON
Zone2
OFF
1 2
ON
Zone3
OFF
1 2
ON
Zone4
OFF
1 2
6. Setting Procedure for Central Control Address
Turn on the main powers of all air conditioners.
After completing test run of the air conditioners, set central control
addresses as follows.
(Central control addresses will be automatically set in increasing order of Unit No.)
Automatic setting
1.Automatic registration
of central control
addresses by
Serial-Parallel I/O:
C2
Carry out each input after the display return to the normal mode, and
check the operating status of each air conditioner. The number shown on
the setting display is the central control address and the Unit No. of the air
conditioner.
7 - 190
Mini ECO-i System
Remote Control Functions
SW1
Setting
8
1
8
display
Central Address System Indoor
Setting
Button
Back Forward
Central control address registration switch
Switch No8 Test
Mode
Be sure to use
the unit with the
6
7
8
Normal mode
switch turned off.
Manual Central control
address registration :
Switch No 7
Auto Central control
Spare
address registration :
Be sure to use the
unit
with
the
switch turned off.
Switching of a main unit and a sub unit
under centralized control
Main unit: OFF Sub unit: ON
For normal use, the main unit is turned
off. In use with the AMY adaptor, the
Switch No.
1
2
intelligent controller, and the system
controller, turn on the sub unit.
OFF
OFF
ON
OFF
Switch No 3
OFF
ON
Spare
Be sure to use
ON
ON
the unit with the
switch turned off.
Central control address 1-16
1
2
3
Central control address 17-32
17
18
19
Central control address 33-48
33
34
35
Central control address 49-64
49
50
51
Set central control addresses automatically?
Set addresses through the wired remote controller?
Central control
Central control
addresses are manually
addresses are manually
set through
set through the wired
Serial-Parallel I/O.
remote controller.
2.Manual registration of
central control
addresses:
C1
Main circuit board
(Code
Date 1 Data 2)
Set
Cancel
Switch No.
5
6
OFF OFF
ON OFF
OFF ON
Switch No 4
16
32
48
64
Manual setting
3.Registration of central
control addresses
through the wired
remote controller