9. LonWorks Interface Product Manual
(SHA-LN16UG(B))
1. LonWorks Interface Overview
Product Overview
This interface is a communications interface for connecting
LonWorks to an air conditioner unit (PAC, GHP) control
network.
From the host connected to LonWorks, basic settings and
status monitoring is possible for up to 16 groups of A/C units.
System Diagram
Indoor/outdoor unit
control line
x Up to 16 groups of indoor units (maximum 64 units) can be controlled with 1 LonWorks Interface unit.
For 17 or more groups of indoor units, connect additional interface units.
x Install a remote controller (or system controller, etc.), which can control the A/C units, to an indoor/outdoor
unit line other than the LonWorks Interface unit.
x Before making the connection to the LonWorks Interface unit, set the central control addresses in the indoor
units.
LonWorks
communication line
LonWorks Interface
7 - 135