Sanyo MINI ECO-i SPW-CR365GXH56B Service Manual page 237

Hide thumbs Also See for MINI ECO-i SPW-CR365GXH56B:
Table of Contents

Advertisement

11. Schedule Timer
(SHA-TM64AG(B))
S42
Remote Controller Enable Items (1)
1
If remote controller enable/disable is used,
this switch sets the range for remote
2
controller enable (cancel).
3
Enable all items* that can be controlled
with the remote controller.
4
5
Enable only the items determined by
setting switches 2, 3, and 4.
6
This switch should be OFF for normal use,
7
or when remote controller enable/disable is
8
not used.
* This refers to the following items: start/stop,
OFF
ON
operation mode, temperature setting, flap,
* These switches
and fan speed.
are all OFF at the
time of delivery.
Remote Controller Disable Item Switches (2, 3, 4)
When timer remote controller disable is used, set the remote controller
disable item switches according to the items for which remote
controller operation will be disabled.
Remote controller disabled items
Remote controller disable not used
Start/stop
Operation mode
Operation mode + Start/stop
Temperature setting
Temperature setting + Start/stop
Temperature setting + Operation mode
Temperature setting + Operation mode + Start/stop
Central 1 – 4 are the designations for the remote-controller disable
modes for the system controller.
Simultaneous time communications (5)
When multiple schedule timers are installed, set this switch to ON to
perform time settings for multiple units simultaneously. One minute
after the time is set, the time at the other schedule timers will change
to match the set time. (Ordinarily this switch is OFF.)
Spare (6, 7, 8)
Be sure that these switches are OFF when the system is used.
OFF
ON
2
3
OFF OFF
Central 1
OFF OFF
Central 4
OFF
ON
OFF
ON
ON
OFF
ON
OFF
Central 3
ON
ON
ON
ON
Central 2
Disabled: OFF Enabled: ON
Creating Timer Groups
The schedule timer can be set for 6 time status changes. These can be
used to create up to 8 groups (timer groups). For systems in which sched-
ule timers are used, set the timer groups to match the central control
addresses of the indoor units that will be subject to group timer control.
The timer-group settings for the schedule timer involve assignment of
central control addresses. Therefore, use the system controller (or other
central control device) or wired remote controllers to set the central con-
trol addresses of the indoor units, then make the schedule timer settings.
[Setting fixed timer groups]
Schedule timer
2
1
Central control address 1 – 8
18
17
4
Central control address 17 – 24
OFF
ON
OFF
ON
33
34
OFF
ON
Central control address 33 – 40
OFF
ON
49
50
Central control address 49 – 56
7 - 177
Mini ECO-i System
Remote Control Functions
1 fixed timer group (64 units together)
4 fixed timer group (16 units together)
8 fixed timer group (8 units together)
Central control address 1 – 64
8
9
10
Central control address 9 – 16
Central control address 1 – 16
24
25
26
Central control address 25 – 32
Central control address 17 – 32
40
41
42
Central control address 41 – 48
Central control address 33 – 48
56
57
58
Central control address 57 – 64
Central control address 49 – 64
16
32
48
64
7