Application
The CVM03050 equipment controllers are designed for variable air volume (VAV) box applications.
CVM03050 controllers operate on an RS-485 BACnet
Controllers (B-AACs) and integrate into Johnson Controls
CVM03050 controllers feature an integral damper actuator, a digital Differential Pressure
Transmitter (DPT) sensor, and a 32-bit microprocessor. The CVM03050-0P model features an
integral potentiometer to sense actual VAV box damper position. These controllers also include an
integral real-time clock, which enables the controllers to monitor and control schedules, calendars,
and trends, and operate for extended periods of time as stand-alone controllers when offline
from the Facility Explorer
wireless network sensors for zone and discharge air temperature sensing. Their small package
size facilitates quick field installation and efficient use of space without compromising control
performance.
Figure 1: F4-CVM3050
Communications protocols
The CVM03050 controllers can communicate using BACnet MS/TP, N2, or wireless Zigbee
default, the CVM controllers communicate using the BACnet MS/TP protocol. The BACnet protocol
is a standard for ANSI, ASHRAE, and the International Standards Organization (ISO) for building
controls.
Part No. 24-10143-01809 Rev. B
2019-05-17
F4-CVM VAV Terminal Equipment
Controllers Installation Instructions
system network. These controllers connect easily to the wired and
®
MS/TP bus as BACnet Advanced Application
®
and third-party BACnet systems.
®
*241014301809B*
F4-CVM03050-0, F4-CVM03050-0P
. By
®
(barcode for factory use only)

Advertisement

Table of Contents
loading

Summary of Contents for Johnson Controls F4-CVM

  • Page 1 The CVM03050 equipment controllers are designed for variable air volume (VAV) box applications. CVM03050 controllers operate on an RS-485 BACnet MS/TP bus as BACnet Advanced Application ® Controllers (B-AACs) and integrate into Johnson Controls and third-party BACnet systems. ® CVM03050 controllers feature an integral damper actuator, a digital Differential Pressure Transmitter (DPT) sensor, and a 32-bit microprocessor.
  • Page 2: North American Emissions Compliance

    • Do not drop the controller or subject it to physical shock. Parts included • One CVM03050 controller with removable terminal blocks (Input/Output, Power, FC, and SA bus are removable) • One installation instructions sheet F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 3: Materials And Special Tools Needed

    • Mount the CVM so that the power transformer and other devices do not radiate excessive heat to the controller. To mount the CVM controllers, complete the following steps: 1. Set all the switches on the equipment controller to their known settings. F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 4 Attach the needed length of tubing (supplied and installed by field personnel) to the dual port fitting on the CVM controller and the other ends of the tubing to the pressure transducer in the VAV box application . F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 5 (VAV) ou le réseau de conduites au démarrage de l'unité de traitement d'air. CVM03050 physical features The following figure displays the physical features of CVM03050, and the accompanying table provides a description of the physical features and a reference to further information where required. F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 6 Voltage Analog Output (0–10 VDC) or Binary Output (24 VAC Triac) (see Table 3) Dual Port Fitting Manual Override Button (see Mounting) Coupler Bolt Controller Coupler (see Mounting) Universal Serial Bus (USB) 2.0 Host Type A Port Note: The USB feature is not currently supported. F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 7 Resistive Analog Inputs (0–600k ohm): 0–2k Potentiometer (see Table 3) RTD: 1k Nickel, 1k Platinum, or A99B SI NTC: 10K Type L (10K Johnson Controls Type II is equivalent to Type L) or 2.252K Type Dry Contact Binary Input Sensor Actuator (SA) Bus Terminal Block: Orange terminal (see...
  • Page 8: Terminal Blocks And Bus Ports

    CVM near the FC and SA terminal blocks. The output terminal blocks are located on the side of the controller near the power supply. For more information about I/O terminal functions, requirements, and ratings, see Table 3. F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 9: Sa Bus Terminal Block

    Use a 4-wire twisted, shielded cable, as shown in Figure 5, to wire the removable SA Bus terminal block plugs on the CVM and other SA Bus devices in a daisy-chain configuration. For more information about SA Bus terminal functions, requirements, and ratings, see Table 4. F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 10: Modular Ports

    The modular SA Bus port provides a connection for the MAP Gateway, ATV7003 VAV Balancing Tool , FX-DIS1710 Local Controller Display, FX-WRZ78xx Series One-to-One Wireless Transmitter, and NS Series sensors. The modular FC Bus port provides a connection for the Bluetooth Commissioning Converter and the FX-ZFR Wireless Router. F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 11: Supply Power Terminal Block

    The CVM does not require an earth ground connection. However, when grounding the secondary of the 24 VAC transformer is required, only one connection to ground must be made near the transformer. See Figure 8. F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 12 Note: If you are using the CVM03050 controller with the Wireless Field Bus System, refer to the WNC1800/FX-ZFR182x Pro Series Wireless Field Bus System Bulletin (LIT-12012378) or the FX-ZFR Series Wireless Field Bus System Bulletin (LIT-12011660). F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 13: Termination Diagrams

    Termination diagrams A set of Johnson Controls termination diagrams provides details for wiring inputs and outputs to the controllers. See the figures in this section for the applicable termination diagrams. Table 2: Termination details Type of Type of Field Input/...
  • Page 14 (Internal Source) 24 VAC Triac Output (Switch Low, External Source) Note: Applies to CO4 and CO5. Incremental Control to Actuator (Switch Low, External Source) Note: Applies to CO4 and CO5. Analog Output (Voltage) F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 15 Note: Applies to BO3 (for only), BO1, and BO2. 24 VAC Binary Output (Switch Low, Internally Sourced) Network Stat with Phone SA Bus Jack (Fixed Address = 199) Network Stat with Terminals SA Bus Addressable F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 16: Terminal Wiring Guidelines, Functions, Ratings, And Requirements

    Use the following figure to estimate the maximum cable length relative to the wire size and the load current (in mA) when wiring inputs and outputs. Note: The following figure applies to low-voltage (<30 V) inputs and outputs only. F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 17: Communications Bus And Supply Power Wiring Guidelines

    • Shielded cable is strongly recommended for all FC and SA bus cables. • Refer to the for detailed information about wire size and cable length requirements for the FC and SA buses. F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 18: I/O Terminal Blocks, Ratings And Requirements

    Table . Internal 12 V, 15k ohm pull up Universal Input Common for all Universal IN terminals Same as (Universal) ICOMn Note: All Universal ICOMn INn. terminals are isolated from all other commons. F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 19 Binary Input Same as (Configurable) common. OCOMn OUTn. Binary Output Signal Common: All Configurable Outputs defined as Binary Outputs are isolated from all other commons, including other Configurable Output commons. F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 20 (Outputs) Internal Power Source: See Guideline C in OCOMn Table . 30 VAC maximum voltage to load 0.5 A maximum output current 1.3 A at 25% duty cycle 40 mA minimum load current F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 21 FC Bus provides 15 VDC Power for: 24 AWG 3-pair CAT 3 Cable FC BUS (Port) FC BUS <30.5m (100 ft) • Wireless Bluetooth Commissioning Converter (BTCVT) • Wireless ZigBee Field Bus Router F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 22 The FC bus and SA bus wiring recommendations in this table are for MS/TP Bus communications at 38.4k baud. The MAP Gateway serves as a replacement for the BTCVT, which is no longer available for purchase, but continues to be supported. F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 23: Setup And Adjustments

    (Connect the FC/SA terminal block on an FX-PCX to an SA bus only.) Important: Before the CVM controller is powered on, connect the FX-ZFR/ZFR Pro Wireless Field Bus Router to the FC bus port (RJ-12 modular jack) on the front of the controller. F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 24: Setting The Device Address

    (MSB) to least significant bit (LSB) when the controller is oriented. . In the following figure, the switches are set to 1 2 3, designating this controller's device address as 123. F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 25: Setting The End-Of-Line (Eol) Switch

    EOL switch to OFF. When a controller is connected to power with its EOL switch set to ON, the amber EOL LED on the controller cover is illuminated. F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 26: Repair Information

    Repair information If the CVM03050 equipment controller fails to operate within its specifications, replace the unit. For a replacement unit, contact the nearest Johnson Controls representative. Troubleshooting equipment controllers Table 5 provides LED status indicator information for troubleshooting the CVM03050 controller.
  • Page 27 SA BUS Green Blink - 2 Hz not supported) On Steady = Communication lost; waiting to join communication ring On Steady = EOL is active Amber Off Steady = EOL is not active F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 28: General Troubleshooting

    4. Reset the breaker/fuse or replace the transformer. Note: When replacing the transformer, it is recommended to replace with a model that utilizes a resettable circuit breaker. A circuit breaker makes solving wiring problems easier. F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 29 1 V. device and verify the Connect the OCOM terminal of commanded value is The Common Reference is the configurable output to the present. incorrect. common of the connected end device. F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 30: Ordering Information And Accessories

    Bulletin (LIT-12011336) for a list of available products. Transformer, 120/208/240 VAC Primary to 24 VAC Y64T15-0 Secondary, 92 VA, Foot Mount, 72.2 cm (30 in.), Primary Leads and 76.2 cm (30 in.) Secondary Leads, Class 2 F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 31 The FIT can be used to check out the wiring of the MS/ TP RS-485 bus as well as verify proper communications of supervisory controllers and equipment controllers connected to the bus. The FIT can be used on both the FC Bus and SA Bus. F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 32: Technical Specifications

    Device Addressing for BACnet Decimal address set via three rotary switches; valid controller MS/TP device addresses 4-127 Decimal address set via three rotary switches: valid controller Device Addressing for N2 device addresses 1-254 F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 33 SA Bus Modular Ports: RJ-12 6-Pin Modular Jacks Mounts to damper shaft using single set screw and to duct with Mounting single mounting screw Enclosure material: ABS and polycarbonate UL94 5VB; Self- extinguishing Housing Protection Class: IP20 (IEC529) F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 34 The performance specifications are nominal and conform to acceptable industry standard. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products.
  • Page 35: Points Of Single Contact

    JOHNSON CONTROLS JOHNSON CONTROLS JOHNSON CONTROLS C/O CONTROLS PRODUCT MANAGEMENT WESTENDHOF 3 507 E MICHIGAN ST NO. 32 CHANGJIJANG RD NEW DISTRICT 45143 ESSEN MILWAUKEE WI 53202 WUXI JIANGSU PROVINCE 214028 GERMANY CHINA F4-CVM VAV Terminal Equipment Controllers Installation Instructions...
  • Page 36 © 2019 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without notice. www.johnsoncontrols.com...