Basic Installation Procedures
Neutral-to-Ground Bonding
Figure 12 N-G screw
1
2
RJ45 CAT5e/6 network cables
For series stacking (120 and 240 volts), connect an RJ45 CAT5e/6 network cable between the two Sync ports as well as the two
RV-C ports.
Figure 13 Series Stacking Using Two Freedom EX 4000s
D
26
IMPORTANT: In vehicles, the neutral-to-ground bonding
(connection enabled by the N-G screw) near the AC_OUT
terminals (as shown in Figure 12 ) in one of the inverters
(unit 1) in a series stacked configuration must be
disconnected by removing the N-G screw while leaving the
N-G screw in place in the other inverter (unit 2) to allow the
automatic neutral-to-ground switching to continue for the
series stacked pair.
c
Do not connect any wires to the AC INPUT L2 terminals on both units at all when stacking.
A
First Freedom EX 4000
A
B
RJ45 CAT5e/6 network cable connected to
the Sync ports of each Freedom EX 4000
B
C
C
Second Freedom EX 4000
D
RJ45 CAT5e/6 network cable connected to
the RV-C ports of each Freedom EX 4000
Freedom EX 4000 Installation Guide