11.7.6 VIP, Medical, Earthquake Parameters Menu
VIP SERVICE ENABLED - When set to "Yes" the car will treat medical calls from the dispatcher as
VIP calls. Upon assignment of a VIP call the car will be removed from group service, complete
answering any car calls and then proceeds to the VIP call floor. It will remain at the floor until a car
call is entered or the "MED EMG / VIP" door time expires. When set to "No" the car will treat medical
call assignments from the dispatcher as a medical call.
ALLOW NEW CAR CALLS BEFORE VIP PHASE 1 - When a VIP hall call is entered the car is
removed from group operation and will answer all of its car calls before going to the VIP hall call's
floor. When set to "Yes" new car calls can be entered while the car is responding to its existing car
calls. When set to "No" no new car calls can be entered while the car is responding to existing car
calls.
MULTIPLE CAR CALLS DURING VIP PHASE 2 - When set to "Yes" will allow multiple car calls
during VIP Phase 2 service. The car will not return to normal service until all car calls have been
answered and the VIP/Medical Phase II door time has expired. When set to "No" will allow single car
call after VIP Phase 1 has completed. The car will return to normal service once when the car call
has been answered.
VIP/CAR RISER MED PHASE1 DOOR TIME - When the parameter "VIP service enabled" is set to
"No" and the car is answering a medical call that is mapped to the car controller, this parameter will
control the amount of time the car will wait at the medical emergency floor before returning to
normal service.
NOTE 1: If the car is answering a medical call that is mapped to a dispatcher this parameter will
have no effect. When the parameter "VIP service enabled" is set to "Yes" this parameter
will control the amount of time the car will wait at the VIP recall floor before returning to
normal service.
NOTE 2: This parameter is effective for both dispatcher mapped and car mapped VIP calls.
VIP/MEDICAL PHASE2 DOOR TIME (.1SEC)
set to NO, this parameter will control the door time during medical phase 2.When the parameter
"VIP SERVICE ENABLED" is set to "Yes" and the parameter "MULTIPLE CAR CALLS DURING VIP
PHASE 2" is set to "Yes" this parameter will control the door time during VIP phase 2.
MEDICAL PHASE 2 OPENS BOTH DOORS:
When set to "Yes" the car will open both front and rear door simultaneously on Medical Emergency
Phase II.
MEDICAL PHASE 2 OPENS DOOR VIA DOB?
When set to "Yes" the door open button is required to open the doors on Medical Emergency
Phase II.
GROUP CAR AUTOMATIC MEDICAL EMERGENCY?
If set to "Yes" the car is capable of responding to automatic Medical Emergency calls from the
group. Set to "No" if this car cannot answer group Medical Emergency calls.
RETURN IND: Y/N ATT: Y/N CAR ON MED PHASE1?
If parameter is set to "Yes" independent or attendant operated cars may be considered for medical
recall assignments. They will, however, will only be assigned the Medical Emergency if no automatic
cars are available. This parameter should be set to match the same parameter on the dispatcher's
parameter screen.
Revision AA 2.2
Microflite Ultra 2000
-
When the parameter "VIP SERVICE ENABLED" is
Printed 03 - 15 - 03
11 - 23