Cisco 124792 User Manual page 23

Cisco ac/dc power system user guide
Table of Contents

Advertisement

Chapter 1
Introduction
Table 1-4
Protection
Overcurrent (output)
Overvoltage
Table 1-5
Table 1-5
Status & Alarms
Alarm Contacts
Status (Rectifier)
Table 1-6
Table 1-6
Mechanical
Shelf Dimensions
WxHxD
1RU Shelf WxHxD
Mounting
Table 1-7
Table 1-7
Environment
Shock/Vibration
Earthquake
Audible Noise
Ambient Temperature
Storage Temperature
Relative Humidity
Table 1-8
May 2006
Protection Specifications
Description
Short circuit and automatic current limiting
Selective shutdown of modules at excessive
output voltages
provides status and alarm specifications for the Cisco AC/DC Power System.
Status and Alarm Specifications
Description
Four form-C alarm contacts (Low Voltage, Mains
Error, Module Failure, Fuse/Circuit Breaker
Failure), maximum 60 VDC, rated at 1A
Green LED indicates power is within acceptable
range
Yellow LED indicates current limit/thermal
protection
Red LED indicates overvoltage shutdown or
rectifier alarm
provides mechanical specifications of the Cisco AC/DC Power System.
Mechanical Specifications
Description
17.4 x 5.25 x 10.8in. (442 x 132.9 x274mm)
17.1 x 1.69 x 9.175in. (434 x 43 x 233mm)
ETSI, 19in. (IEC and ANSI) or 23in.
provides environmental specifications for the Cisco AC/DC Power System.
Environmental Specifications
Description
(NEBS) Level 3, Class B Certification
Zone 4 Compliant
<60 dBA
-40°C to 55°C
-40°C to +85°C
10-90%, non-condensing
provides compliance specifications for the Cisco AC/DC Power System.
1.1.6 General Specifications
Cisco AC/DC Power System User Guide, R1.0
1-7

Advertisement

Table of Contents
loading

This manual is also suitable for:

124778159330

Table of Contents