Eec Device Variant Restriction - Siemens SIMATIC NET SCALANCE X-200RNA Operating Instructions Manual

Industrial ethernet switches
Hide thumbs Also See for SIMATIC NET SCALANCE X-200RNA:
Table of Contents

Advertisement

Installation and disassembly

6.2 EEC device variant restriction

6.2
EEC device variant restriction
The following information applies only to the EEC variant of the device:
Safety notices when using according to IEC 61131-2
If you use the device supplied with 100 ... 240 V AC according to IEC 61131-2, you must observe
the following safety notices in addition to the general safety notices for protection against
explosion:
According to the requirements of the IEC 61131-2 standard and the EC directive 2006/95/EC
(Low Voltage Directive), the devices are "open equipment" and, in accordance with UL/CSA
certification, they are an "open type".
To fulfill requirements for safe operation with regard to mechanical stability, flame retardation,
stability, and protection against contact, the following alternative types of installation are
specified:
• Installation in a suitable cabinet
• Installation in a suitable enclosure
• Installation in a suitably equipped, enclosed control room
Additional notes
Use only approved components
If you use components and accessories that are not approved for SIMATIC NET devices or their
target systems, this may violate the requirements and regulations for safety and
electromagnetic compatibility.
Only use components approved for the SIMATIC NET devices.
NOTICE
Warming and premature aging of the IE switch due to direct sunlight
Direct sunlight can heat up the device and can lead to premature aging of the IE switch and its
cabling.
Provide suitable shade to protect the IE switch against direct sunlight.
Note
During installation and operation, keep to the installation guidelines and safety notices
described in this document and in the system manuals "Industrial Ethernet / PROFINET Industrial
Ethernet" and "Industrial Ethernet / PROFINET passive network components".
You will find information on the system manuals in the section "Introduction", under "Further
documentation".
60
CAUTION
Operating Instructions, 04/2022, C79000-G8976-C342-07
SCALANCE X-200RNA