Temperature input
Water inlet temperature of energy recovery
Water inlet temperature of energy recovery
Energy recovery water outlet temperature
Energy recovery water outlet temperature
To modify a setting, consult the relevant section in the description of the controller.
Recoverable energy
The recoverable energy can be calculated from:
RECOVERED ENERGY (kW) = 4.2 x water flow (l/s) x water temperature rise (˚C)
In the tables below, typical examples are given.
Data for low temperature rise/high water flow systems
Parameter
Recoverable energy
Recoverable energy
Water flow
Pressure drop
Water flow
Pressure drop
Temperature at inlet
Temperature at inlet
Temperature at outlet
Temperature at outlet
Data for high temperature rise/low water flow systems
Parameter
Recoverable energy
Recoverable energy
Water flow
Pressure drop
Water flow
Pressure drop
Temperature at inlet
Temperature at inlet
Temperature at outlet
Temperature at outlet
92
Unit
+
GA 11
GA 15
kW
9.7
13.2
hp
13.2
18
l/min
13.9
18.9
mbar
50
75
cfm
0.5
0.7
in WC
20
30
˚C
50
50
˚F
122
122
˚C
60
60
˚F
140
140
Unit
+
GA 11
GA 15
kW
9.7
13.2
hp
13.2
18
l/min
3.5
4.7
mbar
10
25
cfm
0.1
0.1
in WC
4
10
˚C
20
20
˚F
68
68
˚C
60
60
˚F
140
140
Minimum
setting
˚C
0
˚F
32
˚C
0
˚F
32
+
+
GA 18
GA 22
15.8
19.4
21.5
26.3
22.7
27.8
150
170
0.8
1
60
68
50
50
122
122
60
60
140
140
+
+
GA 18
GA 22
15.8
19.4
21.5
26.3
5.7
6.9
25
25
0.2
0.2
10
10
20
20
68
68
60
60
140
140
Instruction book
Nominal
Maximum
setting
setting
50
99
122
210
60
99
60
210
GA 30
+
+
GA 26
22.9
26.4
31.1
35.9
32.8
37.9
250
330
1.2
1.3
100
132
50
50
122
122
60
60
140
140
+
+
GA 30
GA 26
22.9
26.4
31.1
35.9
8.2
9.5
35
35
0.3
0.3
14
14
20
20
68
68
60
60
140
140
2920 7118 31