(5) External power supply
Use a reinforced or double insulated CE-marked external power supply, and ground the FG terminal.
(External power supply used for the tests conducted by Mitsubishi: DLP-120-24-1 (manufactured by TDK-
Lambda Corporation), PS5R-SF24 (manufactured by IDEC Corporation))
(6) Power supply modules
• Ground the LG and FG terminals after short-circuiting them.
• Use a CE-marked external power supply with a reinforced insulation or a double insulation to supply 24VDC
(7) I/O modules
• Install a DC power supply and an I/O module inside the same control panel.
• Use a shielded cable for the DC power when it is extended out of the control panel.
• Keep each DC power cable length to 30m or less.
• Take a surge protective measure, such as installing a surge suppressor, if the relay switches five times or
(8) High-speed counter modules
• Install a DC power supply and a high-speed counter module inside the same control panel.
• Use a shielded cable for the DC power when it is extended out of the control panel.
• Keep the length of cables connected to external devices to 30m or less.
(9) Positioning modules
Install a DC power supply and a positioning module inside the same control panel.
(10)Temperature control modules
Install a DC power supply and a temperature control module inside the same control panel.
(11)Flexible high-speed I/O control module
Take following measures.
• Attach a ferrite core to the cable for the DC power connected to the flexible high-speed I/O control module,
• Install the DC power in the same control panel where the module is installed.
• Use a shielded cable when a DC power cable is laid out of the control panel.
• The length of the cable connected to an output part or external devices must be 2m or less for open collector
• The length of the cable connecting an input part and external devices must be 30m or less.
144
Downloaded from
ManualsNet.com
to the L63SP.
more per minute.
and to the cable for the DC power connected to a controller. For a ferrite core, the ESD-SR-250
(manufactured by NEC TOKIN Corporation) is recommended.
output, and 10m or less for differential output.