Mitsubishi Electric MELSEC L Series User Manual page 114

Programmable controller
Hide thumbs Also See for MELSEC L Series:
Table of Contents

Advertisement

(a) Number of devices that can be registered
Up to 32 devices in total can be registered.
(b) Checking the execution status
(c) Forcibly turning on/off from multiple GX Works2
Forced on/off can be registered from multiple GX Works2 to a single head module. In this case, the last
registration is effective. For this reason, the GX Works2 that executed the forced on/off may display an on/off
information that is different from that of the head module. When the forced on/off registration is performed from
multiple GX Works2, click the
(d) Status of devices after forced on/off registration data are canceled
When the on/off registration information of the following input (X) and output (Y) are canceled, the forced on/off
status is retained.
(e) Status of the head module
The REM. LED of the head module flashes.
Forced on/off can be registered regardless of the operating status (RUN/STOP).
If an error occurs in the head module, output (Y) cannot be turned on.
(f) Target input/output
112
Downloaded from
ManualsNet.com
• "Forced Input Output Registration/Cancellation" window of GX Works2
• Flashing of the MODE LED (green) (The MODE LED flashes in green when a device is registered.)
• The on status of the 0 bit in Debug function usage (SD840)
• Of the inputs (X) in the range of unattached modules, input (X) that is outside the refresh range with CC-
Link
• Output (Y) that is outside the range that was set in "RX/RY Setting" of Network Configuration Setting of the
master station
• Input/output (X/Y) of the connected modules
• Input/output (X/Y) of the head module that corresponds to the refresh range of the remote input/output
(RX/RY) of the connected CC-Link master/local module
search engine
button to update the data, and then execute the function.