Error
code
[LINK PARA. ERROR]
A network refresh parameter for CC-Link is out of range.
■Supplementary information
3106
• Common information: File name/Drive name
• Individual information: Parameter No.
■Diagnostic timing
• When powered on or reset
[LINK PARA. ERROR]
• The CC-Link parameter setting is incorrect.
• The mode not available for the installed CC-Link module
version is set.
3107
■Supplementary information
• Common information: File name/Drive name
• Individual information: Parameter No.
■Diagnostic timing
• When powered on or reset
[SP. PARA ERROR]
The start I/O number for the intelligent function module set in GX
Works2 is different from the actual one.
■Supplementary information
3300
• Common information: File name/Drive name
• Individual information: Parameter No.
■Diagnostic timing
• When powered on or reset, or when writing to PLC
[SP. PARA ERROR]
• Auto refresh parameters for the intelligent function module are
out of range.
• The intelligent function module set in GX Works2 is different
3301
from the actually installed module.
■Supplementary information
• Common information: File name/Drive name
• Individual information: Parameter No.
■Diagnostic timing
• When powered on or reset, or when writing to PLC
[SP. PARA ERROR]
Intelligent function module parameters are incorrect.
■Supplementary information
3302
• Common information: File name/Drive name
• Individual information: Parameter No.
■Diagnostic timing
• When powered on or reset, or when writing to PLC
[REMOTE PASS. ERR.]
The start I/O number of the remote password target module is
set to any other than 0000H to 0FF0H.
■Supplementary information
3400
• Common information: -
• Individual information: -
■Diagnostic timing
• When powered on or reset
[REMOTE PASS. ERR.]
The position specified with the start I/O number in the remote
password setting is abnormal.
• No module is installed at the position.
• An intelligent function module other than the serial
3401
communication module is installed at the position.
■Supplementary information
• Common information: -
• Individual information: -
■Diagnostic timing
• When powered on or reset
Downloaded from
ManualsNet.com
Error and cause
search engine
Correct the network parameter settings, and then write them.
If the error occurs again even after the correction, the module may have failed.
(Please consult your local Mitsubishi representative.)
Correct the parameter setting.
Correct the parameter setting.
Correct the parameter setting.
Correct the parameter setting.
Change the start I/O number of the target module to a number within the range
of 0000H to 0FF0H.
Install an intelligent function module that supports the remote password function
in the position specified with the I/O number in the remote password setting.