(c) Grounding a Ver.1.10-compatible CC-Link dedicated cable
Ground the shield of a cable connected to the CC-Link module or any of the CC-Link stations which is the
farthest from the input power inside the control panel within 30cm from the module or station.
Ver.1.10-compatible CC-Link dedicated cable is a shielded cable Strip a part of the jacket of the cable as shown
below and ground the exposed shield to the largest area.
Use the specified Ver.1.10-compatible CC-Link dedicated cable.
Use the FG terminals of the CC-Link module and CC-Link stations as shown below to connect to the FG line
inside the control panel.
Terminating
resistor
(d) Grounding cables with a cable clamp
Use shielded cables for external wiring and ground the shields of the shielded cables to the control panel with
an AD75CK cable clamp (manufactured by Mitsubishi). (Ground the shields within 20 to 30cm from the
module.)
For details on the AD75CK, refer to the following.
Downloaded from
ManualsNet.com
Master module
(Blue)
DA
(White)
DB
(Yellow)
DG
SLD
Ver.1.10-compatible
FG
CC-Link dedicated
cable
Inside the control panel
Module
20 to 30cm
AD75CK
AD75CK-type Cable Clamping Instruction Manual
search engine
Ver.1.10-compatible CC-Link
dedicated cable
Shield
Remote module
(Blue)
(Blue)
DA
(White)
(White)
DB
(Yellow)
(Yellow)
DG
SLD
Ver.1.10-compatible
FG
CC-Link dedicated
cable
APPENDICES
Local module
(Blue)
DA
Terminating
(White)
resistor
DB
(Yellow)
DG
SLD
FG
A
141